Programming the control
signal terminals
09/01 AWB8230-1412GB
74
Signalling relay terminals K11, K12, K14
If a fault occurs, the signalling relay (changeover) is triggered. The
switching conditions can be programmed as required.
Table 18: Default setting of the signalling relay
X Use the above table to configure contacts K11–K12 or K11–K14
as make or break contacts under PNU C33.
After a fault has occurred, the associated fault message is retained
even after the voltage supply is switched off. The fault message
can be displayed again after the voltage has been switched back
on. However, the inverter is reset when the device is switched off,
i.e. the fault message will not be signalled on the terminals of the
signalling relay after the inverter is switched back on.
When the signalling relay output is configured as a break contact
(default setting), it is important to remember that there is a delay
from the time the supply voltage is switched on until the AL output
is closed, and that a fault message for the AL output therefore
appears for a short time after the supply is switched on.
Default setting of the signalling relay Reconfigured signalling relay terminals (PNU C33 = 00)
Fault or DF5 switched off Operating message Fault message Operating message or DF5
switched off
Voltage Operating
status
K11–K12 K11–K14 Voltage Operating
status
K11–K12 K11–K14
On Normal Open Closed On Normal Closed Open
On Fault Closed Open On Fault Open Closed
Off – Closed Open Off – Closed Open
K12K11 K14
K12K11 K14 K12K11 K14
K12K11 K14
PNU Name Adjustable in
RUN mode
Value Function WE
C33 Signalling relay
output
– 00 K11-K14 close with a fault message 01
01 K11-K14 close when the supply voltage is applied
h
If however, the fault signalling is to be retained even after
the inverter is switched back on, a latching (self maintai-
ning) relay should be used.