Programming the control
signal terminals
09/01 AWB8230-1412GB
72
PID controller deviation message OD
The digital output configured as OD is activated when a user defi-
nable PID deviation (actual value versus setpoint value) is
exceeded. The OD output remains active as long as this differential
is exceeded.
X If you want to configure a programmable output as OD, you
must set the threshold under PNU C44 at which the OD signal
should be activated.
X Then, program one or more of the digital outputs 11 or 12 as
the OD output, by setting the value 04 under PNU C21 or C22 .
Figure 73: Digital output 11 configured as OD PID deviation
OD
24 V
50 mA
1112CM2
Figure 74: Function chart for OD PID deviation
a Setpoint
b Actual value
As the digital outputs 11 and 12 are configured as break contacts, OD
is active with 0.
PNU C44
PNU C44
OD
a
b
PNU Name Adjustable in
RUN mode
Value Function WE
C44 PID regulator
deviation
0 to 100% If the deviation between the setpoint and actual value exceeds the
value entered here when the PID controller is active, the OD signal
activates.
3.0