Programming the control
signal terminals
09/01 AWB8230-1412GB
68
Frequency value messages FA1/FA2
The digital output configured as FA1 will be activated as soon as
the setpoint frequency is achieved.
The digital output configured as FA2 is activated as long as the
frequencies set under PNU C42 and C43 are exceeded.
To ensure a certain level of hysterysis, the FA1 and FA2 signals are
activated 0.5 Hz before the frequency setpoint value or the
frequency value set under PNU C42 is achieved and deactivated
1.5 Hz after the frequency setpoint value or the frequency value
set under PNU C43 is achieved.
X If you want to configure a programmable output as FA2, you
must set the frequency under PNU C42, at which the FA2 signal
is to be generated in the acceleration phase.
X With PNU C43, you set the respective frequency which is to
remain active until the FA2 signal is deactivated during decele-
ration.
X Program one of the digital outputs 11 or 12 as an FA1 or FA2
output by setting under PNU C21 or C22, the value 01 for FA1
or 02 for FA2.
Figure 66: Function chart for FA1 (frequency achieved)
f
o
: output frequency
F01: setpoint value
As the digital outputs 11 and 12 are configured as break contacts, FA1
is active with “0”.
Figure 67: Digital output 11 configured as FA1/FA2 (frequency
achieved/exceeded)
FA1
f
O
0.5 Hz
0.5 Hz
60 ms
1.5 Hz
PNU F01
PNU F01
1.5 Hz
60 ms
FA1/FA2
24 V
50 mA
1112CM2
Figure 68: Function chart for FA2 “frequency exceeded”
f
o
: output frequency
As the digital outputs 11 and 12 are configured as break contacts, FA2
is active with “0”.
h
The transition of an FA1 or FA2 signal from the inactive to
the active state takes place with a delay of about 60 ms.
FA2
PNU C42
PNU C43
f
O
0.5 Hz
1.5 Hz
60 ms