Installation
09/01 AWB8230-1412GB
36
Connecting the signalling relay
The following figure indicates the position of the signalling relay.
Table 4: Description of the signalling relay terminals
Table 5: Signalling relay conductor cross-sections and tightening torques
Figure 30: Connecting the signalling relay
a Signalling relay terminals
h
When connecting the signalling relay, support the open
enclosure front.
a
Terminal desig-
nation
Description
K11 Default settings:
• Operating signal: K11-K14 closed.
• Fault message or power supply off:
K11-K12 closed
Characteristics of the relay contacts:
• Maximum 250 V AC/2.5 A (resistive) or 0.2 A (inductive, power factor = 0.4);
Minimum 100 V AC/10 mA
• Maximum 30 V DC/3.0 A (resistive) or 0.7 A (inductive, power factor = 0.4);
Minimum 5 V DC/100 mA
K12
K14
M3
n
mm
2
mm AWG mm Nm
1 x 0.14 to 1.5 6 6 to 16 0.4 x 2.5 0.5 to 0.6
2 x
0.14 to 0.75 6 – 0.4 x 2.5 0.5 to 0.6
K12K11 K14