Messages
09/01 AWB8230-1412GB
104
Other messages
This section describes the messages issued by the DF5 series
frequency inverters in standby mode, when the mains voltage is
switched off, etc.
Display Cause
The frequency inverter is in standby mode
or
a reset signal is active.
The mains voltage has been switched off.
The delay time before automatic restart is
counting down (PNU b01 and b03,
a Section Automatic restart after a
fault, Page 97).
The default settings have been selected and
the frequency inverter is in the initialization
phase (PNU b84 and b85, a Section
Initialization, Page 101, ). The values for
the European market (EU) are being initia-
lized. For non-European models, versions
for North America (USA) and Japan (JP) are
available.
Initialization of the fault history register
Copy station copying in progress.
No data available, e.g. display under
PNU d08 and d09, when the fault history
register is empty the display under
PNU d04, when the PID controller is not
active.