Programming the control
signal terminals
09/01 AWB8230-1412GB
70
RUN operational
The digital output configured as RUN remains activated as long as
a frequency not equal to 0 Hz is present, i.e. as long as the motor
is driven in a clockwise or anticlockwise direction.
X Program one of the digital inputs 11 or 12 as a RUN output by
setting the value 00 under PNU C21 or C22.
Figure 69: Digital output 11 configured as RUN “operational”
RUN
24 V
50 mA
1112CM2
Figure 70: Function chart for RUN “operational”
f
o
: output frequency
a At PNU b82 set start frequency
As the digital outputs 11 and 12 are configured as break contacts, RUN
is active with “0”.
FWD/REV
RUN
f
O
a
a
PNU Name Adjustable in
RUN mode
Value Function WE
b82 Increased start
frequency
– 0.5 to 9.9 Hz An increase in the start frequency leads to a corresponding reduction in
the acceleration and deceleration times (for example to overcome high
frictional resistance). If the frequencies are too high, fault message E02
may be issued. With the set start frequency, the motor starts without a
ramp function.
0.5