Cables and fuses
The cross-sections of the cables and line protection fuses used
must correspond with the applicable standards.
Control cables should be screened with a maximum cross-section
of 0.75 mm
2
.
Use cables with a larger cross-section for supply voltage and motor
cables which exceed about 20 m in length.
Use a cable cross-section of 0.75 mm
2
for the cable which is to be
connected to the signal output. About 5 to 6 mm of the cable ends
should be stripped. The external diameter of the signal cable
should be no more than 2 mm, except for the connection to the
signalling relay.
DF5 Connection to
the power supply
L1, L2, L3, N, U, V, W,
PE (2x)
VDE UL
1)
Moeller mm
2
AWG
322-018 1/3-phase 230 V M10 A 10 A FAZ-1N-B10, PKZM0-10 1.5 15
322-037 1/3-phase 230 V
M10 A 10 A FAZ-1N-B10, PKZM0-10 1.5 15
322-055 1/3-phase 230 V
M10 A 10 A FAZ-1N-B10, PKZM0-10 1.5 15
322-075 1/3-phase 230 V
M16 A 15 A FAZ-1N-B16, PKZM0-16 2.5 13
322-1K1 1/3-phase 230 V
M20 A 20 A FAZ-1N-B20, PKZM0-20 2.5 13
322-1K5 Single-phase 230 V
M25 A 25 A FAZ-1N-B25 4.0 11
3-phase 230 V
M16 A 15 A PKZM0-16 4.0 11
322-2K2 Single-phase 230 V
M40 A 40 A FAZ-1N-B40 4.0 11
3-phase 230 V
M25 A 25 A PKZM0-25 4.0 11
340-037 3-phase 400 V
M10 A 10 A PKZM0-10 1.5 15
340-075
M10 A 10 A PKZM0-10 1.5 15
340-1K5
M10 A 10 A PKZM0-10 1.5 15
340-2K2
M10 A 10 A PKZM0-10 1.5 15
340-3K0
M16 A 15 A PKZM0-16 2.5 13
340-4K0
M16 A 15 A PKZM0-16 2.5 13
340-5K5
M25 A 25 A PKZM0-25 4.0 11
340-7K5
M25 A 25 A PKZM0-25 4.0 11
1) Tripping characteristic H or K5
(approved fuses and fuse holders)