09/01 AWB8230-1412GB
Standard form for user defined
parameter settings
123
PNU Function WE Setpoint
b01 Restart mode
• 00: Fault message
• 01: 0 Hz Start
• 02: Synchronization to current motor speed and
acceleration
• 03: Synchronization and deceleration
00
b02 Permissible power failure duration 1.0
b03 Delay time before restart 1.0
b12 Tripping current for electronic motor protection device I
e
(Inverter)
b13 Characteristic for electronic motor protection device
• 00: Enhanced protection
• 01: Normal protection
01
b21 Motor current limitation
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
01
b22 Tripping current for motor current limitation I
e
x 1.25
b23 Time constant of motor current limitation 1.0
b31 Software dependent parameter protection
• 00: Via SFT input; all functions inhibited
• 01: Via SFT input; function F01 possible
• 02: Without SFT input; all functions inhibited
• 03: Without SFT input; function F01 possible
01
b32 Magnetizing current I
e
x 0.58
b81 Calibration value for voltmeter on FM terminal 80
b82 Increased start frequency
(e.g. with high level of friction)
0.5
b83 Carrier frequency (in kHz) 5.0
b84 Initialization causes
• 00: Clearing of the fault history register
• 01: Selection of the default settings
00
b85 Operating system = 01: European version 01
b86 Frequency factor for display via PNU d07 1.0
b87 OFF key
• 00: Always active
• 01: Not active with control via the FWD/REV
terminals
00
b88 Motor restart after removal of the FRS signal
• 00: With 0 Hz
• 01: With current motor speed
00
b89 Display when a remote operating unit is used
• 01: Actual frequency
• 02: Motor current
• 03: Direction of rotation
• 04: PID actual value
• 05: Status of the digital inputs
• 06: Status of the digital outputs
• 07: Actual frequency multiplied by the frequency
factor
01