09/01 AWB8230-1412GB
Fixed frequency FF1 to FF4
selection
57
Specifying frequency setpoints
The frequency setpoint value can be assigned in one of three ways,
dependent on PNU A01:
• via the installed potentiometer on the keypad,
PNU A01 = 00;
• via analog input O (0 to 10 V) or OI (4 to 20 mA),
PNU A01 = 01 (WE);
• via PNU F01 or PNU A20, PNU A01 = 02.
Selecting fixed frequencies
X The set fixed frequency values are selected by activating the
respective digital inputs (a Table 13).
Table 14: Fixed frequency parameters
PNU Name
Adjustable in
RUN mode
Value Function WE
A01 Defined
frequency
setpoint
– 00 Definition with the potentiometer on the keypad 01
01 Definition via analog input O (0 to 10 V) or OI (4 to 20 mA)
02 Definition under PNU F01 and/or PNU A20
A20 Frequency
setpoint value
j 0.5 to 360 Hz You can input a frequency setpoint value. You must input 02 under
PNU A01 for this purpose.
0.0
A21 Fixed
frequency
You can assign a frequency to each of the 15 fixed frequency parameters
from PNU A21 to A35.
A22
A23
...
A35
F01 Display/input
of frequency
value
Display of the current frequency setpoint value or the current fixed
frequency.
Modified values are saved with the ENTER key according to the selection
of the digital inputs configured as FF1 to FF4.
Resolution g0.1 Hz
h
If one or more of the fixed frequencies exceeds 50 Hz, you
must first increase the end frequency accordingly with
PNU A (04 (a Section ”Maximum end frequency”,
Page 79).
h
Fixed frequency stage 0 (none of the inputs FF1 to FF4 are
activated) corresponds to the frequency setpoint value.
Depending on the configuration PNU A01 it is possible to
implement via the integrated potentiometer, the setpoint
input values O or OI, or via PNU F01 and PNU A20.