EasyManua.ls Logo

Moeller DV6-340 Series - Page 206

Moeller DV6-340 Series
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01/02 AWB8230-1415GB
Standard form for user defined
parameter settings
203
A103 Analog input OI starting current [%] 20 64
A104 Analog input OI end current [%] 100 64
A105 Analog input OI condition for starting frequency
00: Start at PNU A101
02: Start at 0 Hz
01 64
A111 Analog input O2 starting frequency [Hz] 0.00 65
A112 Analog input O2 end frequency [Hz] 0.00 65
A113 Analog input O2 starting voltage [%] 100 65
A114 Analog input O2 end voltage [%] 100 65
A131 Curvature of acceleration characteristic, values from 01
to 10
02 150
A132 Curvature of deceleration characteristic, values from 01
to 10
02 150
PNU Function Units Default Page Setpoint
PNU Function Units Default Page Setpoint
b001 Restart mode
00: Fault message
01: 0 Hz Start
02: Synchronization to current motor speed and
acceleration
03: Synchronization and deceleration
00 153
b002 Permissible power failure duration [s] 1.0 153
b003 Waiting time before restart [s] 1.0 153
b004 Fault message issued immediately
00: No fault on intermittent mains failure
01: Fault on intermittent mains failure
02: No fault on intermittent mains failure at stand-
still and deceleration
00 153
b005 Number of restart attempts
00: 16 restart attempts
01: Unlimited number of restart attempts
00 153
b006 Mains phase failure detection
00: Not active
01: Active
00 153
b007 Synchronization frequency on return of mains power [Hz] 0.00 153
b012 Tripping current for electronic motor protection device [A] I
e
(inverter) 156
b212 Tripping current for electronic motor protection device
(second parameter set)
[A] I
e
(inverter) 156
b312 Tripping current for electronic motor protection device
(third parameter set)
[A] I
e
(inverter) 156
b013 Characteristic for electronic motor protection device
00: Enhanced protection
01: Normal protection
03: User-definable protection
01 156
b213 Characteristic for electronic motor protection device
(second parameter set)
00: Enhanced protection
01: Normal protection
03: User-definable protection
01 156
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616