Appendix
01/02 AWB8230-1415GB
204
b313 Characteristic for electronic motor protection device
(third parameter set)
• 00: Enhanced protection
• 01: Normal protection
• 03: User-definable protection
01 156
b015 Frequency 1 for user-definable motor protection
characteristic
[Hz] 0 156
b016 Tripping current 1 for user-definable motor protection
characteristic
[A] 0.0 156
b017 Frequency 2 for user-definable motor protection
characteristic
[Hz] 0 156
b018 Tripping current 2 for user-definable motor protection
characteristic
[A] 0.0 156
b019 Frequency 3 for user-definable motor protection
characteristic
[Hz] 0 156
b020 Tripping current 3 for user-definable motor protection
characteristic
[A] 0.0 156
b021 Motor current limitation 1
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
• 03: Active in every operating state; in regenerative
operation, the current is increased
• 04: Inactive during acceleration; in regenerative
operation, the current is increased
01 157
b022 Tripping current 1 for motor current limitation [A] I
e
x 1.5 157
b023 Time constant 1 of motor current limitation [s] 1.00 157
b024 Motor current limitation 2
• 00: Inactive
• 01: Active in every operating status
• 02: Inactive during acceleration, otherwise active
• 03: Active in every operating state; in regenerative
operation, the current is increased
• 04: Inactive during acceleration; in regenerative
operation, the current is increased
1 158
b025 Tripping current 1 for motor current limitation [A] I
e
x 1.5 158
b026 Time constant 1 of motor current limitation [s] 1.0 158
b031 Software dependent parameter protection
• 00: Via SFT input; all functions inhibited
• 01: Via SFT input; function F01 possible
• 02: Without SFT input; all functions inhibited
• 03: Without SFT input; function F01 possible
• 10: Extended parameters adjustable in RUN mode
01 159
b034 Running time or Mains On time signal [h] 0 114
b035 Inhibit direction
00: Motor can run in both directions
01: Motor can only run clockwise
02: Motor can only run anticlockwise
00 162
b036 Voltage ramp to starting frequency
• 00: Start without voltage reduction
• 01: Minimum voltage reduction, approx. 6 ms
• ...
• 06: Maximum voltage reduction, approx. 36 ms
06 162
PNU Function Units Default Page Setpoint
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616