Audio Control and Tone (ACT) Module
23-12
ACT Module
*
General
Specifications
Operation Voltage 9 to 16VDC
Power Consumption Refer to Appendix D: ACE3600 Maximum Power Ratings.
Dimensions (H x W x L) 25mm x 95mm x 115mm (1” x 3.6” x 4.5”)
Operating Temperature -30º to +60º C (-22º to +140ºF)
Relative Humidity 0-95% @ 50° C without condensation
User Connection
Power connector Molex 2 pin with polarity
COM IN RS232 Phone 8-pin
COM OUT RS232 Phone 8-pin
Low-level Audio In/Out 4 screw TB connector
High-level In/Out 8 screw TB
Audio
Low-level Audio Input 0.8 to 1.5 Vp-p, 300-3300 Hz, Minimum 50 kΩ ±10%
input impedance – 4.6KV isolated.
Low-level Audio Output 1Vp-p ±60% - 4.6KV isolated, via Isolation Board.
High-level Audio Maximum 0.05 Ω - Impedance
Minimum signal: 100 mV, 100 µA.
High-level Audio Input Maximum 30 VAC RMS, 0.5 A RMS
High-level Audio Output 30 V RMS, 0.5 A RMS maximum per one output
EMC
Electrostatic Discharge IEC 1000-4-2, level 3
Radiated Electromagnetic
Field
IEC 1000-4-3, level 3
Electrical Fast Transient /
Burst
IEC 1000-4-4, level 3
Radiated Emission EN55022
Specifications subject to change without notice.
*
The ACT module is not compliant with RoHS European Directive no. 2002/95/EC.