MANUAL-75-v2.0 69 of 82
Fault code Description Solution
PCS FAULT
Power conversion system
fault.
Power output disabled.
This may occur for a short moment
if the output power is overloaded.
Press the emergency stop button
and then release the button if this
fault persists.
If this action does not clear the
fault, contact Moxion Power.
HV ISOLATION
The high voltage (HV)
isolation is compromised.
Primary functions disabled.
1. Shut down the unit.
2. Check if the neutral is
shorted to the ground or
chassis.
3. Make sure the equipment is
properly installed.
4. Set the unit to
STANDBY
.
5. Press the emergency stop
button, and then release the
button.
If this does not clear the fault, then
contact Moxion Power for details of
any maintenance requests.
ESTOP
The emergency stop button
is depressed.
Twist and release the emergency
stop button to deactivate the
emergency stop fault.
SYSTEM FAULT:
SEE USER MANUAL
An unspecified fault is active,
and the system functionality
may be limited.
Shut down the unit for 30 seconds
and restart.
Contact Moxion Power if the fault
persists.
6 Troubleshooting MP75-600 - User Manual