Appendix
The data in this manual are not binding and may be changed by the manufacturer without notice. Reproduction of this manual, even partial, is strictly prohibited.
FREE-COOLING
0122
FC03 Free-cooling
(for the case of
separete free-
cooling units only)
Fans Fixed step
step/step+autotransf./
regulated/ regulated with
inverter
0123
FC06 Free-cooling
Fans Fixed step
step/step+autotransf./
regulated
0124
Step Fixed 2 1÷4
OTHER SETTINGS
0125
AI01 Password User password User 10 0÷999
SETPOINT
0126
ST02 Setpoint Chiller setpoint 7 °C 4÷20
2nd setpoint 10 °C 4÷20
0127
ST03 Setpoint Heat pump setpoint 45 °C 25÷55
2nd setpoint 50 °C 25÷55
0128
ST04 Compensated
setpoint
Probe
average Bat1
Bat2
Bat1/Bat2/average Bat1 and
Bat2/lower of Bat1 and
Bat2/higher of Bat1 and
Bat2
Max comp. 10 °C -30÷80
0129
ST05 Chiller
compensated
setpoint
Room setpoint 20 °C -30÷80
Differential 5 °C -30÷80
0130
ST06 Heat pump
compensated
setpoint
Room setpoint 10 °C -30÷80
Differential 6 °C -30÷80
0131
ST07 Time band setpoint Band 1 start 0.0 °C 0÷23 0÷59
Chiller setpoint 7 °C 4÷20
Heat pump setpoint 45 °C 25÷55
0132
ST08 Time band setpoint Band 2 start 6.0 °C 0÷23 0÷59
Chiller setpoint 7 °C 4÷20
Heat pump setpoint 45 °C 25÷55
0133
ST09 Time band setpoint Band 3 start 12.0 °C 0÷23 0÷59
Chiller setpoint 7 °C 4÷20
Heat pump setpoint 45 °C 25÷55
Ref. Code Mask Field Level Value UDM Range