5 Parameter
BU 0250 en-3021 147
P550
EEPROM copy order
(EEPROM copy order)
0 ... 3
{ 0 }
Only valid with option: "-EEP" (plug-in EEPROM”):
Devices with option: "-EEP" (In preparation)
are also equipped with an internal EEPROM and a
plug-
in EEPROM ("Memory Module") which operates in parallel to this for the storage and
management of parameter data. The data from the inverter are managed in parallel on both
devices, so that a safe and ra
pid exchange of parameter settings in the device is possible for
commissioning or in case of service.
The data sets saved in the internal EEPROM and in the Memory Module can be copied between
the devices. This includes a PLC program that is present on the inverter.
0 =
No change
2 =
Internal External, the data set is
copied from the internal EEPROM to
the memory module (external
EEPROM)
1 = External → Internal, the data set is
copied from the memory module
(external EEPROM) to the internal
EEPROM
3 = External < - > Internal, the data sets
are exchanged between the two
EEPROMs
Note:
The device always used the data record which is saved in the internal EEPROM.
Pos: 468 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P552 CAN Master Zykluszeit [SK 1x0E, SK 2xxE, SK 2xxE-FDS] @ 2\mod_134693 3835351_388.doc x @ 43776 @ @ 1
P552 [-01]
[-02]
CAN Master cycle
(CAN Master cycle time)
S
0.0 / 0.1 … 100.0 ms
{ all 0.0 }
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
[01] = CAN Master function, Cycle time for system bus master functions
[02] = CANopen Abs. encoder, "CANopen absolute encoder", system bus cycle time of absolute
encoder
With the setting 0 = "Auto" the default value (see table) is used.
According to the Baud rate set, there are different minimum values for the actual cycle time:
Baud rate Minimum value t
Z
Default CAN Master Default CANopen Abs.
10kBaud
10ms
50ms
20ms
20kBaud
10ms
25ms
20ms
50kBaud
5ms
10ms
10ms
100kBaud
2ms
5ms
5ms
125kBaud
2ms
5ms
5ms
250kBaud
1ms
5ms
2ms
500kBaud
1ms
5ms
2ms
1000kBaud:
1ms
5ms
2ms