NORDAC LINK (SK 250E-FDS ... SK 280E-FDS) – Users Manual for Frequency Inverters as Field Distributors
152 BU 0250 en-3021
P704 [-01]
...
[-05]
Volt. last error
(Last voltage error 1...5)
S
0 ... 600 V AC This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 492 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P705 – Zwi schenkreisspannung letzte Störung 1... 5 @ 0\mod_1328170720639_388. docx @ 12433 @ @ 1
P705 [-01]
...
[-05]
Last link circuit error
(Last link circuit error 1...5)
S
0 ... 1000 V DC This parameter stores the link voltage that was being delivered at the time the error occurred. The
values of the last 5 errors are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 493 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700-P799/Parameter P706 – Parameter satz letzte Störung 1.. .5 @ 0\mod_1328170810570_388. docx @ 12456 @ @ 1
P706 [-01]
...
[-05]
P set last error
(Parameter set, last error 1… 5)
S
0 ... 3 This parameter stores the parameter set code that was active when the error occurred. Data for
the previous 5 faults are stored.
The SimpleBox / ControlBox must be used to select the corresponding memory location 1...5-
(Array parameter), and confirmed using the OK / ENTER key to read the stored error code.
Pos: 494 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P707 – Sof tware-Version/- Revision @ 0\mod_132817174345 8_388.docx @ 12479 @ @ 1
P707 [-01]
...
[-03]
Software-Version
(Software version/ revision)
0.0 ... 9999.9 This parameter shows the software and revision
numbers in the FI. This can be significant when
different FIs are assigned the same settings.
Array 03 provides information about any special
versions of the hardware or software A zero
stands for the standard version.
... [-01] = Version number (Vx.x)
... [-02] = Revision number (Rx)
... [-03] = Special version of
hardware/software (0.0)