Program Change – Level One 3. Programming
 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
49
System Edit
The System Edit function is selected by pressing the 3 key. The system edit screen appears as shown 
below.
Use the up and down arrow keys to scroll through the choices for each option and the left and right 
arrow keys to move from option to option.
 
There are nine system function options. The factory default selections and user option selections are 
shown below:
Table  7  System Function Options
Function Default Option Selection
V = Alarm 
Verification
(N)one (Y) 120 seconds
I = Silence Inhibit (N)one
(Y) 60 seconds
1
A = Autosilence (N)one
(Y) 10 minutes
1
P = Presignal (N)one
(Y) 3 minutes with 15 second Acknowledge
1
C = Bell Code  (N)one (M) = March Time
(T) = Temporal
(C) = California
A/U = Annunciators 
with or without 
UDACT
(N)one (Z) = 56 Zones
(ZU) = 56 Zones Annunciator with UDACT
2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT
2
L/P = LCD-2X20 or 
Printer/PC in use
(N)one L = LCD-2X20 Series installed
P = Printer or local PC installed
S = SLC style (4) = Style 4 (6) = Style 6
R = Alarm/Trbl 
Reminder
(N)o (Y)es = Sound onboard piezo every 15 seconds 
during alarm and every two minutes during 
trouble after pressing the 
ACKNOWLEDGE
 or 
SILENCE
 key.
1    Requires prior approval of Local Authority Having Jurisdiction.
2    When the UDACT has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD 
display and printer hardcopy. The history file will also be updated with this information. For zone 
annunciation, up to 56 zones, use AFM Series Annunciators or LDM Series Annunciators. For 198 
point annunciation, use the LDM Series Annunciators.
V=N I=N A=N P=N C=N
A/U=N  L/P=N S=4 R=N