4. Operation Special System Timers
68
 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Waterflow Circuits Operation
If an alarm exists from a monitor module point that has a 
WATERFLOW
 type code, the Alarm Silence key 
will not function.
Disable/Enable Operation
Input points which are disabled do not cause an alarm or any CBE (Control-By-Event) activity. 
Disabled output points are held in the off state. All disabled points are treated as if they were in trouble, 
with the exception being the status label that displays is 
DISABL
.
Wiring Fault
If the SLC is wired and programmed for Style 6 and a single fault occurs, the control panel will detect 
the fault and drive both ends of the line, fully recovering from the fault.  The control panel latches the 
trouble and displays it until the 
SYSTEM
 
RESET
 key is pressed.  The display shows Style 6 trouble type.