Appendix B: Electrical Specifications Electrical Specifications
76
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Appendix B: Electrical Specifications
Electrical Specifications
AC Power
AFP-100: 120 VAC, 60 Hz, 2.3 amps
AFP-100E: 240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG (2.00
mm
2
) with 600 VAC insulation
Battery
The control panel uses only sealed lead-acid batteries for standby power:
Signaling Line Circuit
The SLC (TB6) is supervised and power-limited. It can leave the protected premises, provided an
appropriate surge suppressor is used.
Note: Refer to the Device Compatibility Document for a list of UL-listed compatible surge suppressors).
Notification Appliance Circuits
The control panel provides two NACs (TB1 and TB2) that provide nonregulated, special purpose,
power limited circuitry, with the following:
Alarm, Trouble and Supervisory Relays
Specifications for the relays available from TB3 are:
Maximum Charging Circuit: Normal Flat Charge — 27.6V @ 0.8 amp
Maximum Battery Charger Capacity: 18 Amp Hour
Voltage: 15 VDC nominal, 27.6 VDC maximum
Maximum length: 10,000 ft. (3,000 m) total twisted pair length
Maximum loop current: 250 mA (short circuit) or 100 mA (normal)
Maximum loop resistance: 40 ohms
• Nominal operating voltage: 24 VDC • Maximum voltage drop in wiring: 2.0 VDC
• Current-limit: Fuseless, electronic,
power-limited circuitry
• Current for all external devices: 3.0 amps
expandable to 6.0 amps
• End-of-line resistor: 4.7K ohms, ½
watt (PN 71252 UL-listed) for NACs
• Maximum signaling current per circuit:
2.50 amps
Contact rating: 2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Alarm and Trouble relays: Form-C
Supervisory relay: Form-A