1. Product Description
Overview
The AFP-100 is a compact, cost effective, intelligent FACP (Fire Alarm Control Panel) with an
extensive list of powerful features. The combination of Notifier's addressable devices and the AFP-100
offers the latest in fire protection technology. The power supply and all electronics are contained on a
single circuit board housed in a metal cabinet, providing a complete fire control system for most
applications. Optional modules, such as the RTM-8F and ACM-8R,which plug into the main circuit
board, are available for special functions. Available accessories include LED, graphic and LCD
annunciators, digital communicator, local downloading software and remote power expansion. The
AFP-100E offers the same features as the AFP-100 but allows connections to 220/240 VAC input.
Note: Unless otherwise specified the term “control panel” or AFP-100 refers to both the AFP-100 and the AFP-100E
Fire Alarm Control Panel.
Features
The control panel features the following:
• Single standard SLC loop which meets NFPA Style 4, 6 and 7 requirements
• 198 addressable device capacity (99 detectors and 99 monitor/control modules)
• 56 software zones
• Two main circuit board NACs (Notification Appliance Circuits)
• 300 mA resettable power
• 300 mA nonresettable power
• 3.0 amps NAC power (expandable to 6.0 amps with optional XRM-24)
• 40 character LCD display (backlit)
• Real-time clock/calendar
• History file with 500 event capacity
• Advanced fire technology features:
Automatic device Type Code verification
Auto detector test
Maintenance alert
Point trouble identification
• Three levels of detector sensitivity
• Waterflow (nonsilenceable) selection per module point
• Supervisory (latching or nonlatching) selection per point
• System alarm verification selection
• Walktest with report of two devices set to same address
• Presignal per NFPA 72
• Continuous/March Time/Temporal or California code for main circuit board NACs
• Remote ACK/Silence/Reset/Drill via monitor modules, AFM annunciators or LCD-2X20
Remote Fire Annunciator
• Autoprogram (learn mode) reduces installation time
• Password and key-protected nonvolatile memory
• User programmable password
• Fully programmable from panel keyboard or off-line PC
• Rapid poll algorithm for manual stations (U.S. Patent Pending)
• SLC operates up to 10,000 ft. (3,000 m) or 1,000 ft. (300 m) with untwisted, unshielded wire
(U.S. Patent #5,210,523)
Technical Manuals Online! - http://www.tech-man.com