1. Product Description
Annunciators
22
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Annunciator Fixed Modules
Provide the control panel with discrete display and control points. Fixed modules turn their LEDs on
and off as directed by the CPU, and also report switch activations to the CPU for action. You can only
use one fixed module in a system. Each annunciator’s address is fixed at address 1. Connections are
through an EIA-485 serial connection from TB5 on the control panel.
For information and installation instructions refer to the Annunciator Fixed Module manual.
Annunciator Fixed Module - AFM-16AT
Contains 16 red alarm and 16 yellow trouble LEDs, a system trouble LED,
an Online/Power LED, and a local sounder, and switches for control panel
Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for
systems that require 16 or fewer annunciation points.
Annunciator Fixed Module - AFM-32A
Contains 32 red alarm LEDs, a system trouble LED, an ON LINE/POWER
LED, and a local panel sounder with a silence/acknowledge switch. The
Local Silence/Acknowledge switch functions as local lamp test and silence
for annunciator piezo.
The AFM-32A will not accept expander modules, however multiple
annunciators may be used by setting all annunciators to Receive Only,
except the last AFM-32A in line.
Annunciator Fixed Module - AFM-16A
The same as the AFM-32A except it has 16 red alarm LEDs.
Annunciator Devices
Annunciator Relay Control Module - ACM-8R
Provides the control panel with a mappable relay control module. Relays
can be selected for mapping anywhere in the system memory map (in
groups of eight). Provides eight Form-C relays with 5 A @ 125 VAC
(resistive) or 30 VDC (resistive) and 2 A @ 125 VAC (inductive) contacts.
Tracks any group of eight zones within the system. The module is
externally mounted in an ABS-8R enclosure and is connected to the ACS
(EIA-485) annunciator communications bus, up to 6,000 feet (1,800 m)
away from the control panel. Power-limited, filtered, nonresettable power
must be supplied by the FACP.
For more information and installation instructions refer to the ACM-8R
Annunciator Relay Control Module manual.
AFM-16AT.cdr
AFM-32.cdr
12
3
45678
12
ACM-8R.cdr
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-100 and is the answer not in the manual?

Notifier AFP-100 Specifications

General IconGeneral
BrandNotifier
ModelAFP-100
CategoryFire Alarms
LanguageEnglish

Related product manuals