Program Change – Level Two 3. Programming
 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
53
Open Condition
All intelligent devices on the SLC, as well as the two main circuit board NACs, are monitored for fault 
conditions during Walktest mode. When a new trouble condition occurs, it activates all control modules 
programmed for Walktest and Bell Circuit 1, then shuts them off after an 8 second interval (4 seconds 
longer than alarms). The trouble status label is 'TEST T'.
While in Walktest, the trouble relay is on and the System Trouble LED flashes (as in all of Program and 
Status change operations). The alarm relay is not activated. The LCD displays the following:  
Set Time and Date
From the Program Menu, press the 4 key to display the following screen:  
The first digit of the hours is flashing and may be changed with the numeric pad. The right arrow moves 
to the next digit. The up and down arrows select (A)M or (P)M, day of the week, month, day and year. 
Pressing the 
ENTER
 key stores the time and date and returns to the Level 2 screen.
Check
Program selection 5 performs a check on software zone assignments. The control panel looks for output 
devices assigned to a software zone that does not contain any input devices (detectors, monitor 
modules). If multiple devices fail the check, the up and down arrow keys are used to step through the 
list of devices. The user must return to point editing to correct any errors.
Note: The system continues monitoring alarm conditions during all Programming and Read Status operations with the 
exception of Walktest.
At the completion of system programming, switch SW1 (Write Protect) should be set to the Write 
Protect position to prevent inadvertent changes to programmed features. Slide the switch to the up 
position to select the Write Protect feature.
ENTER START WALKTEST
CHANGE TIME/DATE
10:00 A MON 01/03/00