9 LX inverter
9 - 18
Drive Programming User’s Manual (I580-E2)
9-6 Precautions for Use of Parameters
for Drive Programming
9-6-1 Parameters Affected by Rated Current (%)
Parameter
No.
Description Data
b012 1st Electronic Thermal Level 0.20 to 1.00 x Rated current
b212 2nd Electronic Thermal Level
b016 Free Setting Electronic Thermal Current 1 0.0 to Rated current
b018 Free Setting Electronic Thermal Current 2
b020 Free Setting Electronic Thermal Current 3
b022 1st Overload Limit Level
<Heavy load>
0.20 to 2.00 x Rated current
<Light load>
0.20 to 1.50 x Rated current
b025 1st Overload Limit Level 2
C039 Low Current Detection Level
<Heavy load>
0.00 to 2.00 x Rated current
<Light load>
0.00 to 1.50 x Rated current
C041 1st Overload Warning Level
0.0: Function not active
<Heavy load>
0.00 to 2.00 x Rated current
<Light load>
0.00 to 1.50 x Rated current
C111 1st Overload Warning Level 2
<Heavy load>
0.00 to 2.00 x Rated current
<Light load>
0.00 to 1.50 x Rated current