154
Block Programming Instructions
Section 3-30
ONE CYCLE AND
WAIT
WAIT
805
WAIT(805) Block program
Required
ONE CYCLE AND
WAIT
WAIT
805
WAIT(805)
B
B: Bit operand
If the operand bit is OFF (ON for WAIT NOT(805)), the rest of the
instructions in the block program will be skipped. In the next cycle,
none of the block program will be executed except for the execution
condition for WAIT(805) or WAIT(805) NOT. When the execution condi-
tion goes ON (OFF for WAIT(805) NOT), the instruction from
WAIT(805) or WAIT(805) NOT to the end of the program will be exe-
cuted.
Block program
Required
ONE CYCLE AND
WAIT (NOT)
WAIT NOT
805
WAIT(805) NOT
B
B: Bit operand
If the operand bit is OFF (ON for WAIT NOT(805)), the rest of the
instructions in the block program will be skipped. In the next cycle,
none of the block program will be executed except for the execution
condition for WAIT(805) or WAIT(805) NOT. When the execution condi-
tion goes ON (OFF for WAIT(805) NOT), the instruction from
WAIT(805) or WAIT(805) NOT to the end of the program will be exe-
cuted.
Block program
Required
TIMER WAIT
TIMW
813
(BCD)
TIMWX
816
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
TIMW(813)
N
SV
N: Timer number
SV: Set value
Block program
Required
TIMWX(816)
N
SV
N: Timer number
SV: Set value
Instruction
Mnemonic
Code
Symbol/Operand FunctionS Location
Execution condition
If the execution condition is ON for WAIT(805), the rest of the
instruction in the block program will be skipped.
Execution
condition
OFF
Execution
condition
OFF
Execution
condition
ON
"A"
executed.
Execution
condition
"B" executed
.
"C" executed.
"C"
executed.
"C"
executed.
Wait
BEND
SV
C
Time elapsed.
preset.
Delays execution of the block program until the specified time has
elapsed. Execution continues from the next instruction after
TIMW(813)/TIMWX(816) when the timer times out.
SV: 0 to 999.9 s for BCD and
0 to 6,553.5 s for binary
"A"
executed.
"B" executed.
"C" executed.

Table of Contents