332
Startup Settings and Maintenance Section 6-6
Confirming the User Program Date
The dates the program and parameters were created can be confirmed by
checking the contents of A090 to A097.
Note The CS1G/H-CPU@@ (-V1) and CJ1@-CPU@@ CPU Units do not support
this function.
Auxiliary Area Words
6-6-8 Write-protection from FINS Commands Sent to CPU Units via
Networks
For CS/CJ-series CPU Units Ver. 2.0 or later, protection can be set to prevent
writing to and otherwise controlling CPU Units by using FINS commands via
networks (i.e., connections other than direct serial connections). This includes
writing from applications using FinsGateway as well as from the CX-Program-
mer, CX-Protocol, and CX-Process. Reading will still be possible in this case.
The following operations will be prohibited if write-protection is set: Download-
ing the user program, PLC Setup, I/O memory, or other data; changing the
operating mode; online editing; and any other write or control operations.
Even if write-protection is set, specific nodes can be set as exception to
enable executing write/control operations from them.
Name Address Description
User Program
Date
A090 to
A093
The time and date the user program was last over-
written in memory is given in BCD.
A09000 to A09007 Seconds (00 to 59 BCD)
A09008 to A09015 Minutes (00 to 59 BCD)
A09100 to A09107 Hour (00 to 23 BCD)
A09108 to A09115 Day of month (01 to 31 BCD)
A09200 to A09207 Month (01 to 12 BCD)
A09208 to A09215 Year (00 to 99 BCD)
A09300 to A09307 Day (00 to 06 BCD)
Day of the week:
00: Sunday, 01: Monday,
02: Tuesday, 03: Wednesday,
04: Thursday, 05: Friday,
06: Saturday
Parameter Date A094 to
A097
The time and date the parameters were last overwrit-
ten in memory is given in BCD. The format is the
same as that for the User Program Date given above.
PLC #1
PLC #2
PLC #3
Disabled
Disabled
Disabled
Disabled
Network
Network
Exceptions are set to enable
writing using FINS commands
from specific nodes, e.g., PLC
#3 and computer #2.
Write-access set for
this PLC.
Computer #1
Network
Enabled
Enabled
Protected against being written
by FINS commands sent from
nodes on networks, e.g., cannot
be written from computer #1,
PLC #1, or PLC #2.
Computer #2