44
Basic Concepts Section 2-1
Units Refreshed by FIORF(225)
Note FIORF(225) is supported by the CJ1-H-R CPU Units only.
Units Refreshed by DLNK(226)
Note DLNK(226) is not supported by the CS1G/H-CPU@@(-V1) and CJ1@-
CPU@@ CPU Units.
2-1-11 Program Capacity
The maximum program capacities of the CS/CJ-series CPU Units for all user
programs (i.e., the total capacity of all tasks) are given in the following table.
All capacities are given as the maximum number of steps. The capacities
must not be exceeded, and writing the program will be disabled if an attempt
is made to exceed the capacity.
Each instruction is from 1 to 7 steps long. Refer to 10-5 Instruction Execution
Times and Number of Steps in the Operation Manual for the specific number
Location CPU or Expansion I/O Rack (but not SYSMAC BUS Slave Racks)
Units Basic I/O Units Not refreshed
Special I/O Units Not refreshed
CPU Bus Units
Refreshes words allocated to the Unit in both
the CIO Area and DM Area.
Refreshed
CPU Bus Units Not refreshed
FIORF
&13
Refreshes all of the allocated
CIO and DM Area words.
Special I/O Unit
with unit number 13
Location CPU or Expansion I/O Rack (but not SYSMAC BUS Slave Racks)
Units Basic I/O Units Not refreshed
Special I/O Units Not refreshed
CPU Bus Units
Refreshes the following data:
Words allocated to the Unit in CIO Area
Words allocated to the Unit in DM Area
Data specific to the CPU Bus Unit, such
as data link data or DeviceNet Remote I/O
Communications data
Refreshed
DLNK
#F
Refreshes the allocated CIO
Area words, DM Area words,
and Unit-specific data.
CPU Bus Unit with
unit number F

Table of Contents