CHAPTER 5 PARAMETERS
E5GN
5–16
Manual reset value
The control must be either standard (heating)
control and 2-PID control. The “integral time”
parameter must be set to “0”.
Ă• This parameter sets the required manipulated variable to remove offset during stabiĆ
lization of P or PD control.
Setting Range Unit Default
0.0 to 100.0 % 50.0
FĂRelated parameters
PID / ON/OFF" (initial setting level)
Integral time" (adjustment level)
Hysteresis (OUT1)
Hysteresis (OUT2)
The control must be ON/OFF control.
This parameter sets the hysteresis for ensuring stable operation at ON/OFF switching.
Ă• In a standard control, use the hysteresis (OUT1)" parameter. The hysteresis
(OUT2)" parameter cannot be used.
Ă• In a heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the hysteresis (OUT1)" parameter to set the control output 1 side
hysteresis, and use the hysteresis (OUT2)" parameter to set the control output 2 side
hysteresis.
Ă• The decimal point setting follows the currently set sensor. During analog input, the
decimal point setting follows the decimal point position" setting.
Setting Range Unit Default
0.1 to 999.9 EU 1.0
FĂRelated parameter
PID / ON/OFF" (initial setting level)
Adjustment Level
Function
Setting
See
Function
Setting
See