CHAPTER 5 PARAMETERS
E5GN
516
Manual reset value
The control must be either standard (heating)
control and 2-PID control. The integral time
parameter must be set to 0.
Ă This parameter sets the required manipulated variable to remove offset during stabiĆ
lization of P or PD control.
Setting Range Unit Default
0.0 to 100.0 % 50.0
FĂRelated parameters
PID / ON/OFF" (initial setting level)
Integral time" (adjustment level)
Hysteresis (OUT1)
Hysteresis (OUT2)
The control must be ON/OFF control.
This parameter sets the hysteresis for ensuring stable operation at ON/OFF switching.
Ă In a standard control, use the hysteresis (OUT1)" parameter. The hysteresis
(OUT2)" parameter cannot be used.
Ă In a heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the hysteresis (OUT1)" parameter to set the control output 1 side
hysteresis, and use the hysteresis (OUT2)" parameter to set the control output 2 side
hysteresis.
Ă The decimal point setting follows the currently set sensor. During analog input, the
decimal point setting follows the decimal point position" setting.
Setting Range Unit Default
0.1 to 999.9 EU 1.0
FĂRelated parameter
PID / ON/OFF" (initial setting level)
Adjustment Level
Function
Setting
See
Function
Setting
See