4.8To Move to the Advanced Function Setting Level
E5GN
4–17
4.8 To Move to the Advanced Function Setting Level
To move to the advanced function setting level, you must cancel initial
setting/communications protection" in the protect level.
In the default setting, you cannot move to the advanced function setting
level.
(1) Press the
and keys simultaneously for at least three seconds
in the operation level."
Ă* The key pressing time can be changed in "protect level move time"
(advanced function level).
(2) The controller moves to the protect level, and operation/adjustment
protection" is displayed.
(3) Press the
key once to move to initial setting/communications
protection."
(4) Set the set value to 0"
(5) Press the and keys simultaneously to return to the operaĆ
tion level."
(6) Press the key for at least three seconds to move to the initial setĆ
ting level" from the operation level."
(7) Select the Move to advanced function setting level" parameter by
pressing the key.
(8) Press the key to enter the password (Ć169"), and either press the
key or leave the setting for at least two seconds to move to the
advanced function setting level" from the initial setting level."
“operation/adjust-
ment protection”
Protect level
“initial setting/
communications
protection”
PV/SP
Operation level
Input type
Initial setting level
Move to advanced
function setting
level
Advanced function
setting level