Setting name Setting description
Default
value
Setting
range
Unit Update timing
Ch1 Number of
Samplings Setting
Set the number of samplings per task
period for analog input data.
1
*1
times After the Unit is re-
started
Ch2 Number of
Samplings Setting
Ch3 Number of
Samplings Setting
Ch4 Number of
Samplings Setting
*1.
The meanings of the set values for Ch£ Number of Samplings Setting are as follows.
Set value Meaning
1 1 time
2 2 times
4 4 times
5 5 times
8 8 times
10 10 times
20 20 times
25 25 times
40 40 times
50 50 times
80 80 times
100 100 times
125 125 times
200 200 times
250 250 times
400 400 times
500 500 times
625 625 times
1000 1000 times
Precautions for Changing the Settings
If you change the number of samplings setting, always set I/O allocations with the Sysmac Studio.
Refer to 7-2 Setting I/O Allocations with the Sysmac Studio on page 7 - 14 for the setting procedure.
If no I/O entry that matches the number of samplings setting has been set, a warning icon is displayed
on the following screens in the Sysmac Studio.
Connection made to Screen
CPU Unit CPU and Expansion Racks Tab Page
8 Functions
8 - 9
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
8-4 Number of Samplings Setting
8
8-4-2 Details on the Function