Alarm
−34−
8.2 Warning
The warning types and records can be displayed on the monitor mode.
When a warning generates, the WNG output will be turned ON. The WNG output is not assigned to the output terminal at the
time of shipment. Refer to "Description of I/O signals which can be assigned" on p.31.
The warning records will be cleared by turning off the control DC power supply.
Warning list
Warning
code
Warning type
Motor
movement
Generation condition Remedial action
_wn30
Motor lock
Continue to
operate
The motor output shaft was locked for a
minimum of 1 seconds.
Check the load condition.
_wn6c
Operation error
Stop
While the input terminal was being
ON, the FWD input or REV input was
assigned using the "input function
selection" parameter.
When assigning the FWD input
or REV input, check that the input
terminal to be assigned is being
OFF.
When changing to the other mode after
JOG operation was executed, the FWD
input or REV input was being ON.
Turn both the FWD input and REV
input OFF.