15.1.2 Performance Specifications
Item
Descriptions
Relay type
Transistor type
C14
C30
C60
C14
C30
C60
No. of
contro-
llable
I/O
points
Control unit
14 points
DC input:
8,
Ry output:
6
30 points
DC input:
16,
Ry output:
14
60 points
DC input:
32,
Ry output:
28
14 points
DC input:
8,
Tr output:
6
30 points
DC input:
16,
Tr output:
14
60 points
DC input:
32,
Tr output:
28
When using E16R
expansion I/O units
Max. 30
points
Max. 46
points
Max. 76
points
Max. 30
points
Max. 46
points
Max. 76
points
When using E30R
expansion I/O units
Max. 254
points
(up to 8
units)
Max. 270
points
(up to 8
units)
Max. 300
points
(up to 8
units)
Max. 254
points
(up to 8
units)
Max. 270
points
(up to 8
units)
Max. 300
points
(up to 8
units)
When using FP0
expansion units
Max. 110
points
(up to 3
units)
Max. 126
points
(up to 3
units)
Max. 156
points
(up to 3
units)
Max. 110
points
(up to 3
units)
Max. 126
points
(up to 3
units)
Max. 156
points
(up to 3
units)
Programming method/Control
method
Relay symbol/Cyclic operation
Program memory Built-in Flash ROM (without backup battery)
Program capacity
C14 : 16k steps
C30/C60: 32k steps
No. of
instruction
Basic 111
High-level
216
Operation speed From 0.32 µs/step (by basic instruction)
Base time
0.2 ms
0.24 ms
0.3 ms
0.2 ms
0.23 ms
0.28 ms
I/O refresh + base time
With E16: 0.34 ms x No. of units
With E30: 0.47 ms x No. of units
With expansion FP0 adapter: 1.4 ms + FP0 expansion unit refresh time
Note9)
Operation memory
Relay
External input (X)
Note1)
1760 points (X0 to X109F)
External output (Y)
Note1)
1760 points (Y0 to Y109F)
Internal relay (R)
4096 points (R0 to R255F)
Special internal relay (R) 192 points
Timer/
Counter (T/C)
1024 points
Note2)
(for initial setting, Timer: 1008 points (T0 to T1007), Counter: 16
points (C1008 to C1023))
Timer: can count up to (in units of 1ms, 10ms, 100ms or 1s)× 32767.
Counter: Can count up to 1 to 32767.
Link relay(L) 2048 points (L0 to L127F)
Memory area
Data register (DT)
C14: 12285 words (DT0 to DT12284)
C30/C60: 32765 words (DT0 to DT32764)
Special data register (DT) 374 words 384 words
Link data register (LD)
256 words (LD0 to LD255)
File register None
Index register (I)
14 words (I0 to ID)
Differential points Unlimited points
Master control relay points
(MCR)
256 points
No. of labels (JP and LOOP) 256 points
No. of step ladders
1000 stages
No. of subroutines 500 subroutines