EVOHD+ Installation Guide
13
NOTE: Do not use the same transformer for the control panel and the external power supplies. Do not install modules more than 914m (3000ft) from the control
panel.
Table 2: Milliamps (mA) Limitations For Each Run of Wire
Wire
Gauge
Length
(of each run of
wire)
Available
Milliamps
(mA)
Wire
Gauge
Length
(of each run of
wire)
Available
Milliamps
(mA)
Wire
Gauge
Length
(of each run of
wire)
Available
Milliamps
(mA)
Wire
Gauge
Length
(of each run of
wire)
Available
Milliamps
(mA)
16AWG
(Surface: 1.039 sq. mm)
30 m (100 ft.) 2000
18 AWG
(Surface: 0.823 sq. mm)
30 m (100 ft.)
2000
22 AWG
(Surface: 0.326 sq. mm)
30 m (100 ft.) 1382
24 AWG
(Surface: 0.205 sq. mm)
30m (100 ft.) 869
61 m (200 ft.) 2000
61 m (200 ft.)
1718 61 m (200 ft.) 680 61m (200 ft.) 427
91 m (300 ft.) 1831
91 m (300 ft.)
1151 91 m (300 ft.) 456 91m (300 ft.) 286
122 m (400 ft.) 1366
122 m (400 ft.)
859 122 m (400 ft.) 340 122m (400 ft.) 214
152 m (500 ft.) 1096
152 m (500 ft.)
689 152 m (500 ft.) 273 152m (500 ft.) 171
183 m (600 ft.) 910
183 m (600 ft.)
573 183 m (600 ft.) 227 183m (600 ft.) 142
213 m (700 ft.) 782
213 m (700 ft.)
492 213 m (700 ft.) 195
244 m (800 ft.) 683
244 m (800 ft.)
429 244 m (800 ft.) 170
274 m (900 ft.) 608
274 m (900 ft.)
382 274 m (900 ft.) 151
305 m (1000 ft.) 546
305 m (1000 ft.)
344 305 m (1000 ft.) 136
457 m (1500 ft.) 365
457 m (1500 ft.)
229
610 m (2000 ft.) 273
610 m (2000 ft.)
172
762 m (2500 ft.) 219
762 m (2500 ft.)
138
914 m (3000 ft.) 182
914 m (3000 ft.)
115