82
EVOHD+ Installation Guide
Door Left Open Interval Before Access Alarm
SECTION [010]
Enter any value between 001 and 255 to determine the number of seconds the door may remain open before the Access Alarm is triggered. Default = 60 secs.
Door Left Open Pre-Alarm
SECTION [004]: OPTION [3]
Program the Pre-Alarm timer in section [011].
Option [3] OFF=The Pre-Alarm will not be generated
Option [3] ON=Pre-Alarm is enabled (default)
Door Left Open Pre-Alarm Timer
SECTION [011]
This timer will trigger the Door Left Open Pre-Alarm before the end of the Door Left Open Interval. Enter any value between 001 and 255 to determine the seconds
before the expiry of the Door Left Open Interval that the reader will beep. Default = 15 seconds.
Door Left Open Alarm Feedback
SECTION [004]: OPTIONS [5] AND [6]
Option [5] OFF=The Door Left Open Alarm is silent
Option [5] ON=The Door Left Open Alarm is audible (default)
If option [5] is enabled:
Option [6] OFF=Beep as long as the Door Left Open Alarm is
occurring (default)
Option [6] ON=Door Left Open Alarm follows Beep Timer (section [012])
Beep Timer For Door Left Open Alarm
SECTION [012]
Enter any value between 001 and 255 to determine the number of seconds the Access Alarm will beep. Default = 5 seconds.
Door Forced Open Access Alarm
SECTION [006]: OPTION [3]
When the Door Forced Open Alarm is disabled, the following sections are also disabled:
Option [3] OFF=Door Forced Open Alarm is disabled
(default)
Option [3] ON=Door Forced Open Alarm is enabled
Door Forced Open Feedback
SECTION [004]: OPTIONS [7] AND [8]
Option [7] OFF=Door Forced Open Alarm is silent
Option [7] ON=Door Forced Open Alarm is audible (default)
If option [7] is enabled:
Option [8] OFF=Will beep as long as Door Forced Open Alarm is occurring (default)
Option [8] ON=Door Forced Open Alarm follows Beep Timer. (section [013])
Beep Timer For Door Forced Open Alarm
SECTION [013]
Enter any value between 001 and 255 to determine the number of seconds the Door Forced Open Alarm will beep. Default = 5 seconds.
PIN Entry ON Keypad
SECTION [006]: OPTION [4]
If the Card and Code Access option is enabled in the EVOHD+ control panel, users must present their access control card and then enter their PIN on the K641R
keypad to gain access. The PIN Entry on Keypad option cannot be turned ON and will always be OFF.
Table 21: Door Forced Open Access Alarm
Section
[004]
Option [7] Door Forced Open Alarm
Option [8] Door Forced Open Alarm follows
[013]
Beep Timer for Door Forced Open Alarm
Transformer
Requirements:
Minimum;
16.5VAC; 40VA
Maximum;
16.5VAC; 75VA
Auxiliary Supply
can provide:
typical 600mA
Max. 700mA
typical 600mA
Max. 700mA
Automatic Shut
Down:
1.1A 1.1A
Usable Battery
Charge Currents:
350mA
350mA
850mA max.