3-16 Installing the Drive
650V AC Drive
Motor Thermistor Connections
This input is provided to detect over-temperature in motors fitted with an internal thermistor.
There is no polarity to the thermistor connections.
IMPORTANT: This input provides “Basic” insulation only to the SELV control circuits and assumes the
motor has “Basic” insulation to the windings/mains circuits.
The thermistor type supported is PTC `Type A’ as defined in IEC 34-11 Part 2. The drive uses
the following resistance thresholds:
Rising temperature trip resistance: 1650 to 4000Ω
Falling temperature trip reset resistance: 750 to 1650Ω
If the motor is not fitted with an internal
thermistor, you should disable the thermistor
trip function either by setting INVERT
THERMISTOR INPUT (
S
Ot) to 1, or by
linking the thermistor terminals.
Control Wiring Connections
Control wiring of between 0.08mm
2
(28AWG) and 2.5mm
2
(12AWG) can be used. Ensure all
wiring is rated for the highest system voltage. All control terminals are SELV, i.e. double-
insulated from power circuits.
Application 1 Default Function
(for other Applications refer to Chapter 13: “Applications”)
RS232 port for use with remote-mounted 6521 and 6901
Keypad or programming PC
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
Configurable digital input
Configurable digital input
Not Coast Stop - configurable digital input:
0V = drive may run, 24V = Coast to Stop
DOUT2
Configurable digital input/output
Not Stop
(input):
24V = RUN FWD & RUN REV signals latched
0V = RUN FWD & RUN REV signals not latched
collector
Configurable digital input/output
Jog
(input):
Direction – configurable digital input:
0V = Remote Forward, 24V = Remote Reverse
Run Forward – configurable digital input: 0V = Stop, 24V =
Run
24V supply for digital I/O
Ramp Output – configurable analog output (10mA maximum
loading)
10V reference (10mA maximum loading)
Speed Trim – analog input 2
0-10V, 0-5V
0-20mA, 4-20mA
Speed Setpoint – analog input 1. If unused, tie this input to
0V.
0V reference for analog/digital I/O
* The total current available is 150mA, either individually or as the sum of terminal 6 & 10.