Sequencing Logic  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page B-3 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
State Outputs of the SEQUENCING LOGIC 
Function Block 
The following table shows the states of individual parameters for the SEQUENCING LOGIC function 
block required to produce the condition of  the MAIN SEQ STATE parameter. 
 
START 
DISABLED
START 
ENABLED
SWITCHED 
ON 
READY
ENABLED
F-STOP 
ACTIVE 
TRIP 
ACTIVE 
TRIPPED 
Tripped  FALSE FALSE  FALSE FALSE FALSE FALSE TRUE TRUE 
Running  FALSE FALSE  FALSE FALSE TRUE FALSE FALSE FALSE 
Jogging  FALSE FALSE  FALSE FALSE Note 1  FALSE  FALSE  FALSE 
Stopping  FALSE FALSE  FALSE FALSE Note 2  TRUE  FALSE  FALSE 
Output 
Contactor 
Depends 
on 
previous 
state 
Depends 
on 
previous 
state 
TRUE TRUE TRUE TRUE TRUE FALSE 
Switch On 
Enable 
FALSE TRUE  TRUE TRUE TRUE TRUE TRUE FALSE 
Switched 
On 
FALSE FALSE  TRUE TRUE TRUE TRUE TRUE FALSE 
Ready  FALSE FALSE  FALSE  TRUE TRUE TRUE TRUE FALSE 
Healthy  TRUE  TRUE  TRUE TRUE TRUE TRUE FALSE 
FALSE 
Note 3 
Table B-2  Parameter States for the MAIN SEQ STATE Parameter