Programming  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page D-77 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
PATTERN GEN 
SETUP::MOTOR CONTROL::PATTERN GEN 
Designed for all Motor Control Modes.  
The pattern generator function block allows you to configure the Drive PWM (Pulse Width Modulator) operation. 
Parameter Descriptions 
RANDOM PATTERN 
PREF: 73.01  Default: TRUE  Range: FALSE / TRUE  
This parameter selects between random pattern (quiet motor noise) or the more conventional fixed carrier PWM strategies. 
When TRUE, random pattern is enabled. 
FREQ SELECT  
PREF: 73.02  Default: 3000 Hz  Range: 3000 to 6000 Hz 
This parameter selects the pwm switching frequency of the output power stack.  
The higher the switching frequency, the lower the level of motor audible noise. However, this is only achieved at the expense 
of increased Drive losses and reduced stack current rating. 
DEFLUX DELAY  
PREF: 73.03  Default: 2.0 s  Range: 0.1 to 10.0 s  
Sets the minimum allowed delay between disabling and then re-enabling PWM  production (i.e. stopping and starting the 
drive). 
DRIVE FREQUENCY  
PREF: 73.04  Default: —.xx Hz  Range: —.xx Hz  
The output frequency provided to the motor. 
ACTUAL PWM FREQ  
PREF: 73.05  Default: —. Hz  Range: —. Hz  
The actual pwm switch frequency applied to the motor. This can reduce in overload conditions.