Power Connections - 890CD Common Bus Drive 
Power Connections - 890CD Common Bus Drive 
EARTH/GROUND 
Fix Drive earth connections to  . 
Maximum wire sizes: 
Frame B: 6mm
2
 / 10AWG  
Frame C: 10mm
2
 / 8AWG  
Frame D: 16mm
2
 / 4AWG 
Fix the earth from the Motor to the base of the 
drive. 
Maximum wire sizes: 
Frame B: 4mm
2
 / 12AWG  
Frame C: 10mm
2
 / 8AWG  
Frame D: 16mm
2
 / 4AWG 
Refer to the 890 Installation Kit for earth/ground fixing details. 
Each unit must be permanently earthed according to EN 50178. 
For permanent earthing: one conductor, PE1, of >10mm² cross-section is required; or two individual 
incoming protective earth conductors, PE1 & PE2, of <10mm² cross-section. Each earth conductor must 
be suitable for the fault current according to EN 60204.