Technical Specifications  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page E-7 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
 
Electrical Ratings: 890CS Frame B, 500V   
Output current must not be exceeded under steady state operating conditions. 
FRAME B : 32A AC rms Input Current (nominal power 15kW) 
Model Number 
 890CS/5/0032B 
Operating Voltage 
  208V to 500V ±10% 
Nominal Operating Voltage 
V 208/230  380/415  460  500 
Input Current  
A 32 
Continuous RMS Output Current 
A 40 
Output Power  
 7.5kW/10HP  15kW  25HP  18kW 
Power Loss 
W 105 105 105 105 
Output Overload 
  150% overload for 60 seconds 
Dynamic Brake Current Rating  
A 20 20 20 20 
Input Bridge I
2
t  
A
2
s 1000 
Prospective Short Circuit Current 
kA 65 
FRAME B : 54A AC rms Input Current (nominal power 30kW) 
Model Number 
 890CS/5/0054B 
Operating Voltage 
  208V to 500V ±10% 
Nominal Operating Voltage 
V 208/230  380/415  460  500 
Input Current  
A 54 
Continuous RMS Output Current 
A 65 
Output Power  
 15kW/20HP  30kW  45HP  37kW 
Power Loss 
W 195 195 195 195 
Output Overload 
  150% overload for 60 seconds 
Dynamic Brake Current Rating  
A 40 40 40 40 
Input Bridge I
2
t  
A
2
s 1500 
Prospective Short Circuit Current 
kA 65