E 
FLYCATCHING 
SETUP::MOTOR CONTROL::FLYCATCHING 
Designed for all Motor Control Modes. 
This block performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the 
motor to the desired setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a 
fan to `windmill’. 
Parameter Descriptions 
VHZ ENABLE  
PREF: 69.01  Default: FALSE  Range: FALSE / TRUE  
Enables flycatching in Volts/Hz Control mode when TRUE. 
VECTOR ENABLE  
PREF: 69.15  Default: FALSE  Range: FALSE / TRUE  
Enables flycatching in Vector Control mode when TRUE. 
START MODE  
PREF: 69.02  Default: 0  Range: See below 
The mode of operation for the flycatching sequence software. 
Enumerated Value : Start Mode 
0 : ALWAYS 
1 : TRIP OR POWERUP 
2 : TRIP  
SEARCH MODE  
PREF: 69.03  Default: 0  Range: See below 
The type of speed search carried out by the flycatching sequence. 
Enumerated Value : Search Mode 
0 : BIDIRECTIONAL 
1 : UNIDIRECTIONAL