Technical Specifications 
Page E-26  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Earthing/Safety Details 
Earthing 
Permanent earthing is mandatory on all units. 
Use a copper protective earth conductor 10mm² minimum cross-section, or install a second conductor in 
parallel with the protective conductor to a separate protective earth terminal 
The conductor itself must meet local requirements for a protective earth conductor 
Input Supply 
Details 
(TN) and (IT) 
Drives with or without external filters are suitable for use on earth (TN) or non-earth referenced (IT) 
supplies 
Earth 
Leakage 
Current 
>10mA (all models)