Sequencing Logic 
Page B-8  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
External Control of the Drive 
Communications Command 
When sequencing is in the Remote Comms mode, the sequencing of the Drive is controlled by writing to 
the COMMS COMMAND (PREF 95.05). 
The COMMS COMMAND parameter is a 16-bit word based on standard fieldbus drive profiles. Some bits 
are not implemented in this release (see “Supported” column of the table below). 
Bit  Name  Description  Supported  Required Value 
0  Switch On  OFF1 Operational 
√ 
 
1  (Not) Disable Voltage  OFF2 Coast Stop 
√ 
 
2  (Not) Quick Stop  OFF3 Fast Stop 
√ 
 
3 Enable Operation   
√ 
 
4  Enable Ramp Output  =0 to set ramp output to zero    1 
5  Enable Ramp  =0 to hold ramp    1 
6  Enable Ramp Input  =0 to set ramp input to zero    1 
7  Reset Fault  Reset on 0 to 1 transition 
√ 
 
8       0 
9       0 
10  Remote  =1 to control remotely    1 
11       0 
12       0 
13       0 
14       0 
15       0