Programming 
Page D-136  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
STABILISATION 
SETUP::MOTOR CONTROL::STABILISATION 
Designed for VOLTS/Hz motor Control Mode. 
Enabling this function reduces the problem of unstable running in induction motors. This can be experienced at approximately 
half full speed, and under low load conditions. 
Parameter Descriptions 
ENABLE  
PREF: 25.01  Default: TRUE  Range: FALSE / TRUE