Powering-up the Units  
1.  Apply the 3-phase supply to the 890CS Common Bus Supply.  
 
WARNING   
  The busbar system is LIVE when the 3-phase supply is provided to the 890CS unit, even prior to 
enabling the bus, and even though the the 890CD unit(s) will show no activity. 
 
2.  Select LOCAL mode operation on the 890CS Common Bus Supply: 
3.  Press the 
 key on the 890CS Common Bus Supply to supply DC to the 890CD Common Bus 
Drive(s) (the drive will not turn the motor). 
♦  The red LEDs on the top of each drive unit will light to show DC is present at the busbars. 
♦  The diagnostics on the 890CS keypad will indicate power is present - refer to Chapter 8: "The 
Keypad" - 6511 - Common Bus Supply. 
4.  You MUST carry out an Autotune if you intend to use the drive in Sensorless Vector Fluxing Mode  
or Closed-Loop Vector Mode - go to page 4-
49. If you are using the drive in Volts/Hz Mode (Open-
Loop Drive) an Autotune is not necessary - go to page 4-
54. 
REMOTE 
LOCAL 
Hold the Stop key down until 
the display spells  
Release the key to display 
the previous menu  
for example,Local Setpoint