Technical Specifications  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page E-27 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Cabling Requirements for EMC Compliance 
 
Power Supply 
Cable 
Motor Cable 
External AC Supply 
EMC Filter to Drive 
Cable 
Brake 
Resistor 
Cable 
Signal/Control 
Cable 
Cable Type 
(for EMC Compliance) 
Unscreened 
Screened/ 
armoured 
Screened/ 
armoured 
Screened/
armoured
Screened 
Segregation 
From all other 
wiring (clean)
From all other wiring (noisy) 
From all other 
wiring (sensitive) 
890xx/2/… 
Length Limitations 
Unlimited 
25 meters To achieve 
EN61800-3 Table 9 
restricted distribution 
  25 metres 25 metres 
890xx/5/… 
Unfiltered 
Length Limitations 
Unlimited 
25 meters To achieve 
EN61800-3 Table 11 
I<100 A 
  25 metres 25 metres 
890xx/x/… 
Length Limitations 
With External AC 
Supply EMC Filter 
Unlimited 
50 metres To achieve 
EN61800-3 Table 9 
restricted distribution 
0.3 metres 
25 metres
 
25 metres 
 
Screen to Earth 
Connection 
  Both ends  Both ends  Both ends  Drive end only 
Output Choke    300 metres maximum      
* Maximum motor cable length under any circumstances