Technical Specifications  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page E-39 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
890SD Branch Protection Fuses (North America)
It is recommended that UL Listed (JDDZ) non-renewable cartridge fuses, Class K5 or H; 
or UL Listed (JDRX) renewable cartridge fuse, Class H, are installed upstream of the drive. 
 
Model Number  Input Fuse Rating (A)  Model Number  Input Fuse Rating (A) 
  Constant  Quadratic    Constant  Quadratic 
230VAC BUILD VARIANT 
Frame B  Frame C 
890SD/2/0003B 6  - 890SD/2/0024C 35  - 
890SD/2/0005B 10  -  890SD/2/0030C 45  - 
890SD/2/0007B 15  -       
890SD/2/0011B 20  -       
890SD/2/0016B 25  -       
500VAC BUILD VARIANT 
Frame B  Frame C 
890SD/5/0002B 6  - 890SD/5/0024C 35  - 
890SD/5/0003B 6  - 890SD/5/0030C 40  - 
890SD/5/0004B 10  -  890SD/5/S030C 40  - 
890SD/5/0006B 15  -       
890SD/5/0010B 20  -       
890SD/5/0012B 20  -       
890SD/5/0016B 25  -       
890SD/5/S0016B 25  -       
Frame D   
890SD/5/0039D 45  -       
890SD/5/0045D 60  -       
890SD/5/0059D 70  -