I/O TRIPS 
SETUP::TRIPS::I/O TRIPS 
This function block is designed to operate in conjunction with the Analog and Digital Input function blocks to trip the Drive on 
a loss of setpoint input or safety control input. 
Parameter Descriptions 
INVERT THERMIST 
PREF: 98.01  Default: FALSE  Range: FALSE / TRUE 
Inverts the sense of the motor thermistor input. The default FALSE is normally-closed/low impedance. 
INVERT ENC TRIP 
PREF: 98.02  Default: FALSE  Range: FALSE / TRUE 
Inverts the sense of the encoder fail input on the encoder Technology Box.  
EXT TRIP MODE 
PREF: 98.08  Default: DISABLED  Range: See below 
Determines the special function of digital input 5. 
Enumerated Value : External Trip Mode 
0 : TRIP -  A low at digital input 5 will cause an external trip 
1 : COAST - A low at digital input 5 will cause the motor to coast to stop. The drive will not trip. 
2 : DISABLED - Digital input 5 does not have any special function. 
INPUT 1 BREAK 
PREF: 98.03  Default: FALSE  Range: FALSE / TRUE 
A general purpose signal designed to be internally wired to the function block ANALOG INPUT 3, BREAK parameter. When 
this signal goes TRUE this causes an INPUT 1 BREAK trip to occur, (unless this trip is disabled within the TRIPS STATUS 
function block, see the DISABLE TRIPS parameter). 
This parameter is not saved in the Drive’s non-volatile memory and thus is reset to the default setting at power-up.