890SD Standalone Drive 
Page 5-10  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Step 2: Connecting Power 
In this section we are going to connect the 3-phase supply to the 890SD Standalone Drive(s).  
We'll also connect the motor and the (optional) brake resistor. 
WARNING   
  During commissioning, remove the fuses (or trip the circuit breaker) on your 3-phase supply. 
Make sure the power is OFF, and that it cannot be switched on accidentally whilst you are working. 
Solid-State Short-Circuit Protection 
These devices provide Class 10 motor overload protection. The maximum internal overload proection level 
(current limit) is 150% for 60 seconds in Constant mode. Refer to Appendix D: Programming - CURRENT 
LIMIT for user current limit adjustment information. 
An external motor overload protective device must be provided by the installer where the motor has a full-
load Ampere rating of less than 50% of the drive output rating; or when the MOTOR STALLED trip is 
TRUE (TRIPS STATUS::DISABLE TRIPS>>MOTOR STALLED); or when the STALL TIME parameter 
is increased above 480 seconds. 
 
Refer to the 890 Installation Kit for earth/ground fixing details. Fit the appropriate parts. 
 
Each unit must be permanently earthed according to EN 50178. 
 
For permanent earthing: 
A cross-section conductor of at least 10mm² is required.  This can be achieved either by using a 
single conductor (PE) or by laying a second conductor though separate terminals (PE2 where 
provided) and electrically in parallel.