Technical Specifications  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page E-23 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Electrical Ratings:  890SD Frame B, 380-500V  
Input currents are listed at 400Vac and 50Hz or 460Vac and 60Hz. Suitable for use in a circuit capable of delivering not more 
than 10000 rms Symmetrical Amperes. Motor power, input current and output current must not be exceeded under steady 
state operating conditions. 
Model Number 
890SD/5/0016B 890SD/5/S016B   
Nominal Supply Voltage 
400Vac  460-500Vac  400Vac  460-500Vac     
Motor Power   
7.5kW 10Hp 
7.5kW 10Hp 
 
Input Bridge I
2
t 
A
2
s 
600 
340 
 
Internal Resistor Power Rating   W
not applicable  not applicable   
External Continuous Power Rating   W
2250 2250 
2250 2250 
 
External Minimum Resistor Rating 
Ω
56 56 
56 56 
 
 
Vector Mode 
Input Current   A
21.7 18.7 21.7 18.7     
Output Current @ 3kHz   A
16 14 16 14     
Power Loss @ 3kHz   W
230 205 230 205     
Output Current @ 6kHz   A
13.8 11.7 13.8 11.7     
Power Loss @ 6kHz   W
230 205 230 205     
Output Overload Motoring  150% overload for 60 seconds 
 
Servo Mode 
Input Current   A 17.9  15.4  23.4  20.9 
 
Output Current @ 4kHz   A 12  10  16  14 
 
Power Loss @ 4kHz   W 190  175  215  205 
 
Output Current @ 8kHz   A 9.4  8.1  11.8  9.9 
 
Power Loss @ 8kHz   W 190  175  215  205 
 
Output Overload Motoring  200% overload for 4 seconds 
Notes: 
1) Based on a 10ms rectangular current pulse.        2) Based on 30% duty at a braking resistor appropriate for braking at 100% of drive rated power. 
3) Up to the highest supply voltage that maintains shaft power less than the product power rating, for a typical induction motor. Derated for operation above this supply voltage. 
4) Products take less input current when operated in these modes, than stated.            5) Based on a permanent-magnet motor with efficiency 90% and power factor 0.9.