Programming 
Page D-24  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Parameter Descriptions 
COEFFICIENT A 
PREF: 65.03, 66.03, 67.03, 
68.03 
Default: 1.00  Range: -300.00 to 300.00 
Coefficient used as defined by the formula. 
COEFFICIENT B 
PREF: 65.04, 66.04, 67.04, 
68.04 
Default: 1.00  Range: -300.00 to 300.00 
Coefficient used as defined by the formula. 
COEFFICIENT C 
PREF: 65.05, 66.05, 67.05, 
68.05  
Default: 0.00  Range: -300.00 to 300.00 
Coefficient used as defined by the formula. 
HIGH LIMIT 
PREF: 65.06, 66.06, 67.06, 
68.06 
Default: 0.00  Range: -300.00 to 300.00 
Use high limit to set a maximum value for the modified parameter on the keypad. Setting the HIGH LIMIT lower than or 
equal to the LOW LIMIT makes the parameter “read-only”. 
LOW LIMIT 
PREF: 65.07, 66.07, 67.07, 
68.07 
Default: 0.00  Range: -300.00 to 300.00 
Use low limit to set a minimum value for the modified parameter on the keypad. Setting the HIGH LIMIT higher than or 
equal to the HIGH LIMIT makes the parameter “read-only”. 
UNITS 
PREF: 65.08, 66.08, 67.08, 
68.08 
Default:   Range: max length is 6 chars 
A 6 character label that is displayed as the parameter units.