Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-67
8
9
10
11
B
C
D
1
2
3
4
5
6
7
E
Parameter Descriptions
Set this parameter to match the virtual master simulator with the virtual master direction.
Enumerated Value : Status
0 : RUNS FORWARD set to this if virtual master input is positive
1 : RUNS REVERSE set to this if virtual master input is negative
If this parameter does not match the virtual master direction the simulator will not function.
Z PULSE OFFSET
PREF: 160.5 Default: 0.0000 Range: 0.0000 to 360.0000º
This parameter sets the position in degrees at which the marker pulse (Z pulse) occurs.
VOLTAGE CONTROL, page D-
150.
MOTOR CURRENT
PREF: 27.05 Default: 6.26 A Range: 0.00 to 3276.70 A
This parameter contains the motor nameplate full-load line current.
MAG CURRENT
PREF: 27.06 Default: 2.50 A
Range: 0.00 to 3276.70 A
This parameter contains the motor model no-load line current as determined by the auto-tune.
* NAMEPLATE RPM PREF: 27.07 Default: 1420 rpm Range: 0.0 to 30000.0 rpm
This parameter contains the motor nameplate full-load rated speed. This is the motor speed in rpm at base frequency minus full
load slip.
* MOTOR CONNECTION
PREF: 27.08 Default: 1 Range: See below
This parameter contains the motor nameplate winding connection.
Enumerated Value : Motor Connection
0 : DELTA
1 : STAR